KB-012: nut-exporter crash loops with ACCESS-DENIED¶
Symptom¶
The nut-exporter pod crash loops with Error: Access denied, and UPS metrics
and alerts stop.
Cause¶
nut-exporter relays the UniFi UPS through dummy-ups in repeater mode, which
has no username or password option and needs anonymous reads. UPS
firmware 1.6.4 started enforcing the NUT server's "credential required"
setting, so every read returns ERR ACCESS-DENIED. Logging in from
nut_exporter directly doesn't work either: the UPS answers LIST CLIENT and
GET NUMLOGINS with ERR INVALID-ARGUMENT.
Fix¶
Turn off "credential required" for the NUT server in the UPS settings in UniFi. The pod recovers by itself. Check anonymous reads with:
Seen¶
2026-10-22, after the UPS auto-updated its firmware overnight.