OSD NVMe Failure and Ceph Rebuild

Summary

2026-09-22 to 2026-10-01. The NVMe drive behind osd.2 on k8s-03 hung three times in three days. Ceph stayed available on two replicas, with no data loss, but a second-order RBD blocklist on another node left volumes stuck for hours. The cluster was then rebuilt on Micron 7300 drives and restored from backups, which exposed a cooling problem in k8s-03.

Timeline

  • 2026-09-22 22:56 UTC. The SK hynix PC801 behind osd.2 stopped responding: I/O timeouts, a failed controller reset, then the kernel disabled the device. The PCIe device stayed visible in talosctl get pcidevices, which pointed at a hung controller rather than a dead or unseated card. Ceph went to HEALTH_WARN with 33 PGs undersized. A power cycle (talosctl reboot -m powercycle) brought the drive back, and Rook reactivated the OSD on its existing data.
  • While degraded, k8s-02's kernel RBD client lost a watch and was blocklisted. Every new rbd map on that node then failed with Cannot send after transport endpoint shutdown, so pods and about 23 Kopiur backup jobs stayed stuck for hours after Ceph itself was back to HEALTH_OK. Removing the blocklist entry wasn't enough; rebooting k8s-02 was.
  • 2026-09-23 11:27 UTC and 2026-09-25 21:44 UTC. The same drive hung twice more. Each power cycle fixed it for a while, so a replacement drive was ordered.
  • 2026-09-30. Instead of swapping one drive, all three nodes were reset and the cluster rebuilt on Micron 7300 drives, with cephx moved to aes256k keys. Apps came back from Kopiur and CNPG Barman backups.
  • 2026-10-01. During the backfill, k8s-03's Micron reached 74 °C, close to its 76 °C critical limit, so recovery was paused with nobackfill and norecover. k8s-03 was moved somewhere cooler, and recovery finished at 10:53 UTC with the drive peaking at 69 °C.
  • 2026-10-03. Rack cooling was improved: raised feet, open case bottoms and a 140 mm fan per node aimed at the NVMe drives and RAM. NVMe temperatures dropped by 18 to 23 °C.

Cause

A failing consumer NVMe drive. The rebuild then ran into a node chassis that couldn't cool an enterprise NVMe drive under sustained writes.

What changed

  • Rook only uses Micron 7300 drives, selected by /dev/disk/by-id (#2664, #2669).
  • cephx uses aes256k only; the CSI driver needed a newer image for it (#2670).
  • Fixes found during the restore: the Dragonfly network policy blocked apps on port 6379, node-exporter lost port 9100 to the ephemeral port range (#2671), and Traefik on the NAS had no restart policy, so S3 stayed down after a NAS reboot and CNPG restores failed (#2672).

What to watch

  • Pool health and a node's RBD session are separate. After a degraded period, check ceph osd blocklist ls and look for stuck volume mounts, even when Ceph reports HEALTH_OK.
  • NVMe temperatures. k8s-03's Micron idles around 45 °C since the cooling changes, with a warning at 72 °C. A drift back up points at a fan.
  • Resetting nodes while Ceph has no quorum hangs in unmountPodMounts, because the kernel RBD client can't flush. A hard power-off gets past it.